Aviation Axis stocks 1313773, S1313773, S1764776 - Tripper Circuit Breaker made by Westinghouse Electric Corp with 5925-00-386-0869. Owned and operated by ASAP Semiconductor, we have access to over 2 billion new and after-market parts applicable within the aerospace and defense industries. All our parts are shipped using our premier shipping and supply chain. We offer short lead-times and some of the fastest shipping times in the industry. We are well-equipped to handle any customer situation - including AOG. Submit an RFQ today and expect a response within 15 minutes or less. ASAP - the evolution of purchasing.
Alternative NSN: 5925-00-386-0869 |
Item Name: Tripper Circuit Breaker |
Federal Supply Class (FSC): 5925 Circuit Breakers |
NIIN: 003860869 |
NCB Code: USA (00) |
Manufacturers: Westinghouse Electric Corp |
Part No | Manufacturer | Item Name | QTY | RFQ |
---|---|---|---|---|
1313773 | westinghouse electric corp | tripper circuit breaker | Avl | RFQ |
S1313773 | westinghouse electric corp | tripper circuit breaker | Avl | RFQ |
S1764776 | westinghouse electric corp | tripper circuit breaker | Avl | RFQ |
Technical Characteristics of NSN 5925003860869
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
ABHP | OVERALL LENGTH | 7.750 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 4.250 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 5.125 INCHES NOMINAL |
AKPX | III POLE QUANTITY | 2 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 TERMINAL |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 600.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 200.0 ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 120.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 420.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 SCREW |