NSN - 5925-01-096-4663, 5925010964663 of Circuit Breaker
Aviation Axis stocks EHB 3030L, EHB3030, EHD3030, EHD3030L, EHD3030L 30A 3POLE - Circuit Breaker made by Westinghouse Electric Corp, Valad Electric Heating Corp, Eaton Aerospace Ltd, Federal Specifications with 5925-01-096-4663. Owned and operated by ASAP Semiconductor, we have access to over 2 billion new and after-market parts applicable within the aerospace and defense industries. All our parts are shipped using our premier shipping and supply chain. We offer short lead-times and some of the fastest shipping times in the industry. We are well-equipped to handle any customer situation - including AOG. Submit an RFQ today and expect a response within 15 minutes or less. ASAP - the evolution of purchasing.
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH
3.375 INCHES NOMINAL
AEBQ
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH
1.000 INCHES NOMINAL
AEBV
UNTHREADED MOUNTING HOLE DIAMETER
0.188 INCHES NOMINAL
AEBY
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH
4.500 INCHES NOMINAL
AEHA
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH
1.000 INCHES NOMINAL
AFJN
FRAGILITY FACTOR
MODERATELY RUGGED
AJEC
BOSS HEIGHT
0.125 INCHES NOMINAL
AKPX
POLE QUANTITY
3
AXHR
MOUNTING FACILITY TYPE AND QUANTITY
4 UNTHREADED HOLE
BBRG
STORAGE TYPE
GENERAL PURPOSE WAREHOUSE
BBRJ
SPECIAL HANDLING FEATURE
MAGNETIC
CPLM
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE
30.0 AMPERES AC ALL LOCATIONS
CPRF
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS
480.0 AC ALL LOCATIONS
CPRG
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS
14000.0 AC ALL LOCATIONS
CPRH
CIRCUIT PROTECTION TYPE
OVERCURRENT ALL LOCATIONS
CPRJ
TRIP RELEASE METHOD
THERMAL-MAGNETIC ALL LOCATIONS
CPRL
TRIP RELEASE CHARACTERISTIC
TIME DELAY ALL LOCATIONS
CPRN
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT
135.0 ALL LOCATIONS
CPRQ
RESET METHOD
MANUAL
CPRR
MAIN CONTACT TRIPPING MECHANISM TYPE
TRIP FREE
CPRT
MANUAL ACTUATOR TYPE AND QUANTITY
1 TOGGLE
CPRW
ACTUATOR FUNCTION
TRIP-RESET
CPRX
ACTUATOR POSITION DESIGNATION
AT POLE TWO
CQWN
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT
2.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CQXF
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED
CORROSION RESISTANT
CRCF
TRIP RELEASE AMBIENT TEMP RATING
40.0 DEG CELSIUS NOMINAL ALL LOCATIONS
FREQ
FREQUENCY IN HERTZ
60.0 ALL LOCATIONS
TEST
TEST DATA DOCUMENT
81348-W-C-375 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING G
TTQY
TERMINAL TYPE AND QUANTITY
6 COMPRESSION
ZZZK
SPECIFICATION/STANDARD DATA
81348-W-C-375/18 GOVERNMENT SPECIFICATION
Related NSN List for 5925-01-096-4663, 5925010964663
We use cookies to ensure that we give you the best experience on our website. If you continue to use this site we will assume that you are happy with it.